.SH "NAME"
phoenixcontact_modbus \- Driver for Phoenix Contact
.SH "SYNOPSIS"
.sp
\fBphoenixcontact_modbus\fR \-h
.sp
\fBphoenixcontact_modbus\fR \-a \fIDEVICE_NAME\fR [\fIOPTIONS\fR]
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
This man page only documents the hardware\-specific features of the phoenixcontact_modbus driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.sp .5v
.RE
.SH "SUPPORTED HARDWARE"
.sp
This driver should support the PhoenixContact QUINT\-UPS industrial DC UPS, model 2320461 and all compatible models\&. More information about this UPS can be found among Internet resources below\&.
.sp
phoenixcontact_modbus uses the libmodbus project, for Modbus implementation\&.
.SH "HOW TO CONFIGURE THE UPS"
.sp
Note: this UPS and its manual refers to Low\-Batt as "Shutdown Event"\&.
.sp
You need the "IFS\-RS232\-DATACABLE" to communicate with the UPS in Linux as the IFS\-USB cable doesn\(cqt seem to be supported\&. FYI communication parameters are: 115200,E,8,1\&.
.sp
You also need the UPS\-CONF Windows software (free; download from their site), to configure the UPS signals and timers\&.
.sp
.RS 4
.ie n \{\
\h'-04' 1.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 1." 4.2
.\}
Run the UPS\-CONF
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 2.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 2." 4.2
.\}
Go to Settings→Time Setting
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 3.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 3." 4.2
.\}
Choose "state of charge shutdown delay"
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 4.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 4." 4.2
.\}
Choose Remote starts PC\-Shutdown in Mains and Battery mode
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 5.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 5." 4.2
.\}
On the PC\-Shutdown enter the maximum value (5 minutes)
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 6.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 6." 4.2
.\}
On the PC\-Restart delay enter the time you want the UPS to leave the output power off before restarting (e\&.g\&. 60 seconds), after mains power is restored\&.
.RE
.sp
.RS 4
.ie n \{\
\h'-04' 7.\h'+01'\c
.\}
.el \{\
.sp -1
.IP " 7." 4.2
.\}
On the UPS, turn the screw to the "PC\-MODE" position
.RE
.sp
Configuring the above way ensures that:
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
When power is lost, UPS constantly calculates remaining battery time
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
When remaining battery time is less than 5 minutes (PC\-Shutdown setting), it will raise the "Shutdown" event (seen as LOW\-BATT in NUT)
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
From that moment even if input power is restored, the UPS will cut the output power to its load after 5 minutes
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
When the input power is restored, the UPS will restore output power after 60 seconds (PC\-RESTART delay setting)\&.
.RE
.sp
Meaning of settings:
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
PC\-Shutdown: How long before output cutoff the UPS will raise the "shutdown event" signal\&. Max value for this is 5 minutes\&. So PC should be able to shutdown within 5 minutes\&.
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
PC\-Restart: How long to delay output power after power is restored\&. Max is 60 seconds\&.
.RE
.SH "EXTRA ARGUMENTS"
.sp
This driver doesn\(cqt support any optional settings\&.
.SH "INSTALLATION"
.sp
This driver may be not built by default\&. You can build it by installing libmodbus and running configure \-\-with\-modbus=yes\&.
.sp
You also need to give proper permissions on the local serial device file (/dev/ttyS0 for example) to allow the NUT user to access it\&.
.SH "INSTANT COMMANDS"
.sp
This driver doesn\(cqt support any instant commands\&.
.SH "CONFIGURABLE VARIABLES"
.sp
The following variables can be set in the NUT configuration as default\&.* values to override or monitor UPS behavior using the phoenixcontact_modbus driver\&.
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
As of NUT v2\&.8\&.4, there is currently no support for run\-time setting of these values (e\&.g\&. with \fBupsrw\fR(8))\&. Currently they are only considered once, during driver initialization\&.
.sp .5v
.RE
.PP
\fBbattery\&.energysave\&.delay\fR=\fInum\fR
.RS 4
Time after entering battery mode before PC shutdown signal is triggered by the UPS (in seconds)\&.
.RE
.PP
\fBups\&.timer\&.shutdown\fR=\fInum\fR
.RS 4
Time allowed for PC to shutdown (in seconds)\&. Maximum is 300 seconds\&.
.RE
.PP
\fBups\&.timer\&.start\fR=\fInum\fR
.RS 4
Duration for which output power remains turned off before rebooting the PC system back on (in seconds)\&.
.RE
.PP
\fBups\&.delay\&.start\fR=\fInum\fR
.RS 4
Delay before switching back to mains after power is restored (in seconds)\&. The mains voltage must be within the threshold for this time, to initiate automatic PC restart\&.
.RE
.PP
\fBexperimental\&.ups\&.mode\&.selector\fR=\fInum\fR
.RS 4
UPS operating mode\&. For example,
9
corresponds to PC\-Mode (vendor\-defined)\&.
.RE
.PP
\fBexperimental\&.battery\&.warning_soh\fR=\fInum\fR
.RS 4
Battery warning threshold for State of Health, in percent\&.
.RE
.PP
\fBinput\&.voltage\&.low\&.critical\fR=\fInum\fR
.RS 4
Threshold voltage (in V) below which the UPS will switch to battery mode\&.
.RE
.PP
\fBinput\&.voltage\&.high\&.critical\fR=\fInum\fR
.RS 4
Voltage threshold (in V) above which the UPS will consider mains power restored (see also below)\&.
.RE
.SH "AUTHORS"
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
Spiros Ioannou
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
Ricardo Rodriguez
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
Ulfat Hasangarayev
.RE
.SH "SEE ALSO"
.SS "The core driver:"
.sp
\fBnutupsdrv\fR(8)
.SS "Internet resources:"
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
The NUT (Network UPS Tools) home page:
https://www\&.networkupstools\&.org/historic/v2\&.8\&.5/
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
libmodbus home page:
http://libmodbus\&.org
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
More information about PhoenixContact QUINT\-UPS industrial DC UPS, model 2320461 UPS series can be found here:
https://www\&.phoenixcontact\&.com/online/portal/us?uri=pxc\-oc\-itemdetail:pid=2320461
.RE